DI4 Four Channel Digital Input Module Technical Data Sheet

The DI4 is a four channel digital input module supporting contact closure or voltage logic inputs. When using input sensors such a proximity detectors, 24V power supply outputs can be optionally used to power the sensor.

Main DI4 Characteristics  
Number of channels
4
Compatible terminal blocks
D12
Group of input channels
1 group
Digital input voltage
24 Vdc
Input logic type
Positive logic (sink)
Digital input number
4 configurable type 2 or type 3 conforming to IEC 61131-2
Input wiring mode
1, 2 or 3 wires
Digital input current
2.3 mA (type 3)
6.32 mA (type 2)
Current state 0 guaranteed
<= 1.5 mA
Current state 1 guaranteed
>= 2 mA (type 3)
>= 6 mA (type 2)
Voltage state 0 guaranteed <5 Vdc
Voltage state 1 guaranteed
11 to 30 Vdc
Input impedance
8 kΩ Type 3
3.58 kΩ Type 2
Input filtering
0 to 20 ms de-bounce configurable in 0.1 ms step
Paralleling of inputs
Yes
Input diagnostic
Field power supply not detected
Sensor power supply not detected
Power supply type
Bus power from power supply bus (24 Vdc)
Field power from power supply field (24 Vdc)
Typical current consumption
27.6 mA at 24 Vdc on the Bus current
1.2 mA at 24 Vdc on the internal field current minimum, with all channels disconnected
501.4 mA at 24 Vdc on the internal field current maximum, with all connected and maximum field sensor current
Power dissipation 1.3 W maximum at 24 Vdc
Isolation
Between channels None
Between channels and bus 1500 Vac
Between channels and ground 1500 Vac
Maximum cable length
Unshielded Maximum length 30 m (98' 5")
Shielded Maximum length 1000 m (656' 2.4")
Net weight
0.045 kg (1.59 oz)
Hot swap
Yes
Housing color
Grey
Environment  
IP degree of protection
IP20
Product certification
CE
CULus
RCM
Standards
EN/IEC 61326-1
EN 61010-2-201
UL 61010-2-201
Directives
2014/30/EU - Electromagnetic compatibility
2014/35/EU - Low voltage
2011/65/EU, 2015/863/EU RoHS
Operating temperature
0 to 55 °C (32 to 131 °F)
Storage temperature
-5 to 60 °C (23 to 140 °F)
Relative humidity
5 % to 95 % without condensation
Operating altitude
0 to 2000 m (0 to 6561 ft)
Pollution degree
2
Vibration
2 g
Shock
15 g for 11 ms

Derating

Note - Derating only requires consideration if using the sensor power supply.
With 200 mA for sensor power supply load
4 channels Type 3 up to 55 °C (131 °F)
4 channels Type 2 up to 40 °C (104 °F)
3 channels Type 2 from 40 to 45 °C (104 to 113 °F)
2 channels Type 2 from 45 to 55 °C (113 to 131 °F)
2 channels Type 3 and 1 channel Type 2 up to 55 °C (131 °F)
With 500 mA for sensor power supply load
4 channels Type 3 up to 50 °C (122 °F)
4 channels Type 2 up to 40°C (104 °F)
3 channels Type 2 from 40 to 45 °C (104 to 113 °F)
3 channels Type 3 from 50 to 55°C (122 to 131°F)
2 channels Type 2 from 45 to 50 °C (113 to 122 °F)
2 channels Type 3 and 1 channel Type 2 up to 50 °C (122 °F)
1 channel Type 2 from 50 to 55 °C (122 to 131 °F)

Dimensions

Dimension Size
a 15 mm (0.59")
b 100 mm (3.94")
c 66 mm (2.60")
c plus Terminal Block 101.9 mm (3.98")

DI4 Four Channel Digital Input Terminal Wiring

DANGER

HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH

  • Do not exceed the device’s ratings.

  • Ensure all cables and wiring harness are secured using a relevant strain relief mechanism.

Failure to follow these instructions will result in death or serious injury

 

WARNING

UNINTENDED EQUIPMENT OPERATION

  • Ensure wires are routed to minimize the pick-up of Electromagnetic interference (EMI) keeping cable lengths to a minimum.

  • Only use copper cables (except for the thermocouple wiring).

Failure to follow these instructions can result in death, serious injury, or equipment damage

Tip - Where signal and power wiring cannot be separated, signal wiring should be shielded.
Terminal Wiring Cross Section
1 solid conductor 0.2 to 2.5 mm² (American Wire Gauge (AWG) 24 - AWG 14)
2 solid conductors 0.2 to 1.5 mm² (AWG 24 - AWG 16) - both conductors must be the same cross section
1 stranded conductor without ferrule 0.2 to 2.5 mm² (AWG 24 - AWG 14)
1 stranded conductor with single ferrule 0.2 to 1.5 mm² (AWG 24 - AWG 16)
2 stranded conductors with twin ferrule 0.2 to 0.75 mm² (AWG 24 - AWG 20)
Note - Minimum individual conductor size in stranded connectors when no ferrule is used is a cross section of 0.05 mm² (AWG 30).

Terminal block captive screws are not supplied tightened and must be tightened to 0.5 to 0.6 Nm (0.30 lb-ft) using a flat tipped screwdriver with a diameter of 3.5 mm (0.14"). Stripping length for all cable types is 10 mm (0.39").

CAUTION

UNINTENDED EQUIPMENT BEHAVIOR

Use the sensor and actuator power supply only for supplying power to sensors or actuators connected to the module.

Failure to follow these instructions can result in injury or equipment damage

Key Description
1 The sensor power outputs, pins 1, 3, 5 and 7, are protected within the module by a common self-resetting eFuse (nominally 500 mA). The module has two power supply diagnostics flags, one for the field power incoming from the backplate, and one for the outgoing power to the sensor.
2 SELV 24 V PSU
3 External fast blow fuse appropriate for load, or protection to an equivalent level