DI4 Four Channel Digital Input Module Technical Data Sheet
The DI4 is a four channel digital input module supporting contact closure or voltage logic inputs. When using input sensors such a proximity detectors, 24V power supply outputs can be optionally used to power the sensor.
| Number of channels |
|
| Compatible terminal blocks |
|
| Group of input channels |
|
| Digital input voltage |
|
| Input logic type |
|
| Digital input number |
| 4 configurable type 2 or type 3 conforming to IEC 61131-2 |
|
| Input wiring mode |
|
| Digital input current |
| 2.3 mA (type 3) |
| 6.32 mA (type 2) |
|
| Current state 0 guaranteed |
|
| Current state 1 guaranteed |
| >= 2 mA (type 3) |
| >= 6 mA (type 2) |
|
| Voltage state 0 guaranteed |
<5 Vdc |
| Voltage state 1 guaranteed |
|
| Input impedance |
| 8 kΩ Type 3 |
| 3.58 kΩ Type 2 |
|
| Input filtering |
| 0 to 20 ms de-bounce configurable in 0.1 ms step |
|
| Paralleling of inputs |
|
| Input diagnostic |
| Field power supply not detected |
| Sensor power supply not detected |
|
| Power supply type |
| Bus power from power supply bus (24 Vdc) |
| Field power from power supply field (24 Vdc) |
|
| Typical current consumption |
| 27.6 mA at 24 Vdc on the Bus current |
| 1.2 mA at 24 Vdc on the internal field current minimum, with all channels disconnected |
| 501.4 mA at 24 Vdc on the internal field current maximum, with all connected and maximum field sensor current |
|
| Power dissipation |
1.3 W maximum at 24 Vdc |
| Isolation |
| Between channels |
None |
| Between channels and bus |
1500 Vac |
| Between channels and ground |
1500 Vac |
|
| Maximum cable length |
| Unshielded |
Maximum length 30 m (98' 5") |
| Shielded |
Maximum length 1000 m (656' 2.4") |
|
| Net weight |
|
| Hot swap |
|
| Housing color |
|
| IP degree of protection |
|
| Product certification |
|
| Standards |
| EN/IEC 61326-1 |
| EN 61010-2-201 |
| UL 61010-2-201 |
|
| Directives |
| 2014/30/EU - Electromagnetic compatibility |
| 2014/35/EU - Low voltage |
| 2011/65/EU, 2015/863/EU RoHS |
|
| Operating temperature |
| 0 to 55 °C (32 to 131 °F) |
|
| Storage temperature |
| -5 to 60 °C (23 to 140 °F) |
|
| Relative humidity |
| 5 % to 95 % without condensation |
|
| Operating altitude |
| 0 to 2000 m (0 to 6561 ft) |
|
| Pollution degree |
|
| Vibration |
|
| Shock |
|
Derating
Note - Derating only requires consideration if using the sensor power supply.
| 4 channels Type 3 up to 55 °C (131 °F) |
| 4 channels Type 2 up to 40 °C (104 °F) |
| 3 channels Type 2 from 40 to 45 °C (104 to 113 °F) |
| 2 channels Type 2 from 45 to 55 °C (113 to 131 °F) |
| 2 channels Type 3 and 1 channel Type 2 up to 55 °C (131 °F) |
|
| 4 channels Type 3 up to 50 °C (122 °F) |
| 4 channels Type 2 up to 40°C (104 °F) |
| 3 channels Type 2 from 40 to 45 °C (104 to 113 °F) |
| 3 channels Type 3 from 50 to 55°C (122 to 131°F) |
| 2 channels Type 2 from 45 to 50 °C (113 to 122 °F) |
| 2 channels Type 3 and 1 channel Type 2 up to 50 °C (122 °F) |
| 1 channel Type 2 from 50 to 55 °C (122 to 131 °F) |
|
Dimensions
| a |
15 mm (0.59") |
| b |
100 mm (3.94") |
| c |
66 mm (2.60") |
| c plus Terminal Block |
101.9 mm (3.98") |
|
DI4 Four Channel Digital Input Terminal Wiring
|
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Failure to follow these instructions will result in death or serious injury
|
|
UNINTENDED EQUIPMENT OPERATION
Failure to follow these instructions can result in death, serious injury, or equipment damage
|
Tip - Where signal and power wiring cannot be separated, signal wiring should be shielded.
| 1 solid conductor |
0.2 to 2.5 mm² (American Wire Gauge (AWG) 24 - AWG 14) |
| 2 solid conductors |
0.2 to 1.5 mm² (AWG 24 - AWG 16) - both conductors must be the same cross section |
| 1 stranded conductor without ferrule |
0.2 to 2.5 mm² (AWG 24 - AWG 14) |
| 1 stranded conductor with single ferrule |
0.2 to 1.5 mm² (AWG 24 - AWG 16) |
| 2 stranded conductors with twin ferrule |
0.2 to 0.75 mm² (AWG 24 - AWG 20) |
Note - Minimum individual conductor size in stranded connectors when no ferrule is used is a cross section of 0.05 mm² (AWG 30).
Terminal block captive screws are not supplied tightened and must be tightened to 0.5 to 0.6 Nm (0.30 lb-ft) using a flat tipped screwdriver with a diameter of 3.5 mm (0.14"). Stripping length for all cable types is 10 mm (0.39").
|
UNINTENDED EQUIPMENT BEHAVIOR
Use the sensor and actuator power supply only for supplying power to sensors or actuators connected to the module.
Failure to follow these instructions can result in injury or equipment damage
|
| 1
|
The sensor power outputs, pins 1, 3, 5 and 7, are protected within the module by a common self-resetting eFuse (nominally 500 mA). The module has two power supply diagnostics flags, one for the field power incoming from the backplate, and one for the outgoing power to the sensor. |
| 2
|
SELV 24 V PSU |
| 3
|
External fast blow fuse appropriate for load, or protection to an equivalent level |
Last update - April 2026