How do I configure a Job?
This user-case example, details how to configure a Job that displays a message on the screen of any connected EPM Data User Interface when an I/O Channel's input goes over or falls under a set threshold value:
Step One - Set up the I/O
The following steps outline briefly how to set-up the I/O.
-
Insert an AI3 module into the first slot of the EPM Data Management device.
-
Login to the EPM Data User Interface, see Logging in for details.
-
Discover and Add the AI3, see Discovering I/O Modules for details.
-
From the first channel on the AI3, set its descriptor to be 'Temperature Sensor', see I/O Channels for details.
Step Two - Configuring the Alarms
The next steps create two alarms, a high alarm and a low alarm. The input to these alarms is the first channel on the AI3 module. These alarms activate when the AI exceeds 80 or falls below 20:
-
Add an alarm to that channel with the Alarm Type 'Temperature Sensor High Alarm', see Configuring an Alarm for details.
-
Set the Alarm to have a Trigger Condition Type of Absolute High.
-
Set the Alarm Threshold to be '80', this is the value that when exceeded, the alarm activates.
-
Select the Temperature Sensor Channel again and add another alarm to the channel with descriptor 'Temperature Sensor Low Alarm'.
-
Set the Alarm to have a trigger type of Absolute Low.
-
Set the Alarm Threshold to be '20'.
-
Once complete, select Review pending changes
screen to review updates to the configuration, and submit them. See Reviewing and Submitting Changes for details if required.Note - Reviewing and submitting can be completed in bulk once you have completed all your additions and/or updates.
Step Three - Configuring the Job and Action
Within EPM Data Management, actions are attached to jobs, you must therefore set up a Job before you can configure an action.
To configure a Job with an associated action:
-
From the Jobs screen, create a Job with the Descriptor of 'Temperature Alarms', see Configuring Jobs for details.
-
From Trigger sources - action conditions, from Source 1 - Select source choose Alarms Process - Temperature Sensor/High.
-
Select Add
to create Source 2. -
From Trigger sources - action conditions, from Source 2 - Select source choose Alarms Process - Temperature Sensor/Low.
Note - Ensure neither source are inverted. -
From Operation to apply, select OR.
-
Select Add action and the new action displays under the Temperature Alarms Job in the Jobs pane.
-
Select the new action and ??????